| Drinking Water and Groundwater Bureau
Environmental
Fact Sheet |
![]() |
| WD-DWGB-11-1 | 2007 |
|
Cross-Connection Control Programs The New Hampshire Code of Administrative Rules Env-Ws 364 Backflow Prevention requires each public water system serving 1,000 or more persons to have an approved, written Cross-Connection Control Program. Such a program can have many elements. The following is an example of a model Cross-Connection Control Program, which satisfies the minimum established criteria. Model Cross Connection Program I. Purpose Cross-connections between water supplies and non-portable sources of contamination can represent one of the most significant threats to health in the water supply industry. These program regulations are designed to maintain the safety and potability of the water in the (city or town) water system by establishing rules and procedures to control cross-connection situations and to prevent the contamination of public drinking water by the backflow of water or other fluids from a source or sources other than its intended or approved source(s) of supply. A. The purpose of this regulation is:
This document is intended to supplement the rules promulgated by the New Hampshire Department of Environmental Service (DES) as listed in section II below. II. Authority A. New Hampshire Administrative Rule Env-Ws 364, Backflow Prevention B. The (city or town) water department rules and regulations, adopted. III. Requirements The water superintendent shall be responsible for the protection of the public potable water distribution system from contamination or pollution due to the backflow or back-siphonage of contaminants or pollution through the water service connection. If, in the judgment of the water superintendent, an approved backflow prevention device is required at the (city’s or town’s) water service connection to any customer’s premises for the safety of the water system; the water superintendent or his designated agent shall give notice, in writing, to said customer to install an approved backflow prevention device at each service connection to his premises. The customer shall, within 90 days, install approved device or devices at his own expense; and failure, refusal, or inability on the part of the customer to install said device or devices within 90 days shall constitute a ground for discontinuing water service to the premises until such device or devices have been properly installed. lV. Definitions A. Approved – Accepted by the water superintendent as meeting an applicable specification stated or cited in this regulation, or as suitable for the proposed use. B. Auxiliary Water Supply – Any water supply on or available to the premises other than the purveyor’s approved public potable water supply. C. Backflow – The flow of water or other fluids, mixtures or substances into the distributing pipes of a portable water supply system form any source other than intended approved source of supply. D. Backflow Preventer – A device or means designed to prevent backflow or back-siphonage.
E. Backpressure – A condition in which the owner’s system pressure is greater than the supplier’s system pressure. F. Back-Siphonage – The flow of water or other fluids, mixtures or substances into the distribution pipes of a potable water supply system from any source other than its intended source caused by the sudden reduction of pressure in the potable water supply system. G. Containment – A method of backflow prevention which requires a backflow prevention device at the water service entrance. H. Contaminant – A substance that will impair the quality of the water to a degree that it creates a serious health hazard to the public leading to poisoning or the spread of disease. I. Cross-Connection – Any actual or potential connection between the public water supply and a source of contamination or pollution. J. Department – New Hampshire Department of Environmental Services (DES). K. Fixture Isolation – A method of backflow prevention in which a backflow preventer is located to correct a cross-connection at an in-plant location rather than at a water service entrance. L. Owner – Any person who has legal title to, or license to operate or habitat in, a property upon which a cross-connection inspection is to be made or upon which a cross-connection is present. M. Person – Any individual, partnership, company public or private corporation political subdivision or agency of the State, department, agency or instrumentality or the Unites States or any other legal entity. N. Permit – A document issued by the water supplier which allows the use of a backflow preventer. O. Pollutant- A foreign substance, that if permitted to get into the public water system, will degrade its quality so as to constitute a moderate hazard, or impair the usefulness or quality of the water to a degree which does not create an actual hazard to the public health; but which does adversely and unreasonably effect such water for domestic use. P. Water Service Entrance – That point in the owner’s water system beyond the sanitary control of the water supplier; generally considered to be the outlet end of the water meter and always before any unprotected branch. Q. Water Superintendent – The official, or his delegated representative in charge of the (city or town) water department is invested with the authority and responsibility for the implementation of an effective cross-connection control program and for the enforcement of the provisions of this ordinance. R. Water Supplier – The public water supply system. V. Administration A. The (city or town) water department will operate a cross-connection control program, to include the keeping of necessary records, which fulfills the requirements of the DES’s Backflow Control Rules and is approved by DES. B. The owner shall allow his property to be inspected for possible cross-connections and shall follow the provisions of the (city or town) water department’s program and the DES’s rules, if a cross-connection is permitted. C. If the (city or town) water department requires that the public supply be protected by containment, the owner shall be responsible for the water quality beyond the outlet end of the containment device and should utilize fixture outlet protection for that purpose. D. The owner may utilize trained or experienced personnel to assist him in the selection of proper fixture outlet devices, and the proper installation of these devices. E. Both the (city or town) water department and the owner shall attempt to eliminate all cross-connections. VI. Responsibilities A. (City or Town) Water Department
B. Owner
VII. Degree of Hazard The (city or town) water department recognizes the threat to the public water system arising from cross-connections. All threats will be classified by degree of hazard and will require the installation of approved backflow prevention devices for high and low hazards. A. Low Degree of Hazard If backflow were to occur, the resulting effect on the water supply would be a change in its aesthetic qualities. The foreign substance must be non-toxic to human. B. High Degree of Hazard If backflow were to occur, the resulting effect on the water supply could cause illness or death if consumed by humans. The foreign substance may be toxic to humans rather from a chemical, bacteriological or radiological standpoint. The effects of the contaminants may result from short or long term exposure. Only the following types of backflow prevention devices may be used for the containment of on-site contaminants for high and low hazard situations respectively: C. High Hazard:
D. Low Hazard:
VIII. Permits The (city or town) water department shall not permit a cross-connection within the public water supply system unless it is considered necessary and that it cannot be eliminated. A. Cross-connection permits that are required for each backflow prevention device are obtained from the (city or town) water department. A fee of [ ] dollars will be charged for the initial permit and [ ] dollars for the renewal of each permit. B. Permits shall be renewed every [ ] years and are non-transferable. Permits are subject to revocation and become immediately revoked if the owner should so change the type of cross-connection or degree of hazard associated with the service. C. A permit is not required when fixture isolation is achieved with the utilization of a non-testable backflow preventer. IX. Existing in-use Backflow Devices Any existing backflow preventer shall be allowed by the (city or town) water department to continue in service unless the degree of hazard is such as to supersede the effectiveness of the present backflow preventer, or result in an unreasonable risk to the public health. X. Periodic Testing A. Backflow prevention devices shall be inspected and tested at least semi-annually for high hazard devices and annually for low hazard devices. B. Periodic inspections shall be performed by the (city or town) water department’s certified inspector or his delegated representative. The inspections will be done at the owner’s expense. C. The inspections shall be conducted during the (city or town) water department’s regular business hours. Exceptions to this, when at the request of the owner, may require additional charges to cover the increased costs to the (city or town) water department. D. Any backflow preventer which fails during a periodic inspection will be repaired or replaced. When repairs are necessary, upon completion of the repair the device will be inspected a second time at the owner’s expense to insure correct operation. High hazard situations will not be allowed to continue unprotected, if the backflow preventer fails the inspection and cannot be repaired immediately. In other situations, a compliance date of not more than [30] days after the inspection date will be established. The owner is responsible for spare parts, repair tools, or a replacement device. Parallel installation of two devices is an effective means of the owner insuring that uninterrupted water service during inspections or repair of devices; and is strongly recommended when the owner desires such continuity. E. These devices shall be repaired or replaced at the expense of the owner whenever said devices are found to be defective. Tests and repairs shall be recorded on forms approved by the water superintendent; and copies distributed to the owner and water superintendent within [ ] days of the actual test. F. Backflow prevention devices will be inspected more frequently than specified in A. above, in cases where there is a history of test failures and the (city or town) water department feels that due to the degree of hazard involved, additional inspections are warranted. Cost of the additional inspections will be borne by the owner. XI. Records and Reports A. Records – The (city or town) water department will initiate and maintain the following:
B. Reports – The (city or town) water department will submit the following to DES:
XII. Fees and Charges The (city or town) water department will publish a list of fees or charges for the following permits: A. Fees
B. Charges
Addendum I. Residential Dual Check A. Effective the date of acceptance of this Cross-Connection Control Program for the (city of town), all new residential buildings will be required to install a residential dual check valve device immediately downstream of the water meter. Installation of this residential dual check valve device on a retrofit basis on existing service lines will be instituted at a time and at a potential cost to the homeowner as deemed necessary by the (city or town) water department. B. The owner should be aware that installation of a residential dual check valve results in a potential closed plumbing system with the residence. As such, provisions may have to be made by the owner to provide for thermal expansion within the closed loop system, i.e., the installation of thermal expansion devices and/or pressure relief valves. II. Strainers A. The (city or town) water department strongly recommends that all new retrofit installations of reduced pressure principle devices and double check valve backflow preventers include the installation of strainers located immediately upstream of the device to prevent fouling of backflow devices due to unforeseen circumstances occurring to the water supply system such as water main repairs, water main breaks, fires, periodic cleaning and flushing of mains, etc. These occurrences may ‘stir up’ debris within the water main that will cause fouling of backflow devices installed without the benefit of strainers. For Additional Information Please contact the Drinking Water and Groundwater Bureau at (603) 271-2513 or dwgbinfo@des.state.nh.us or visit our website at www.des.nh.gov/dwgb. All of the bureau’s fact sheets are on-line at www.des.nh.gov/dwg.htm. Note: This fact sheet is accurate as of January 2007. Statutory or regulatory changes, or the availability of additional information after this date may render this information inaccurate or incomplete. |